UN 223-1PH32-0XB0

SM 1223 Digital input/output Module which is similar as Siemens S7-1200 PLC
1) SM 1223 Digital input/output 8DI 24V DC/ 8DO Relay
2) Compatible with Siemens 6es7
223-1PH32-0XB0
3) Digital module;
4) Could connect with Siemens 1200 CPU and Modules;
5) 3-year warranty;
6) 2-3 working days after payment can ship;
7) Material: ABS, IC

SKU: 5269e416ad31Categories: UniMAT, Unimat PLC controllers SERIESBrand: UniMAT
Model SM 1223
DI 8×24 V DC 
DQ 8×RLY
Order number UN 223-1PH32-0XB0
dimensionWxHxD(mm) 45x100x75
weight 230 g 
Power consumption 5.5 W
Current consumption (SM bus) 145 mA
Current consumption (24VDC) Each point input used is 4mA
7mA per relay coil used
Digital input
Enter points 8
Type Sink/Source type (IEC Class 1 sink type)
Rated voltage 24V DC at 4 mA, nominal
Allowed continuous voltage Max 30V DC
Surge voltage 35VDC, lasting 0.5s
Logic 1 signal (minimum) 2. 15V DC at 5mA
Logic 0 signal (maximum) 5 V DC at 1 mA
Isolation (field side and logic side) 707VDC (type test)
Isolation group 2
Filter time 0.2, 0.4, 0.8, 1.6, 3.2, 6.4 and 12.8ms (selectable, 4 in a group)
Number of inputs connected simultaneously 8
Cable length (meter) 500 (shielded); 300 (unshielded)
Digital output
Output points 8
Type Relay, dry contact
Voltage range 5-30VDC or 5-250VAC                                                                               
Logic 1 signal at maximum current
Logic 0 signal with 10 KQ load
Current (maximum) 2.0A
Lamp load 30 W DC/200 WAC                                                                           
On-state contact resistance 0.2 Ω maximum for new equipment
Leakage current per point
Inrush current 7A with contacts closed
Overload protection None
Isolation (field side and logic side) 1500VAC (coil and contacts)
None (coil and logic side)
Isolation group 2                                                                  
Current at each common terminal 10 A
Inductor clamping voltage                                                                                                          
Switching delay Maximum 10 ms
Mechanical life (no load) 10,000,000 open/close cycles                                                            
Contact life under rated load 100,000 open/close cycles
Behavior during RUN-STOP Previous value or replacement value (default value is 0)
Number of outputs switched on simultaneously 8
Cable length (meter) 500(shielded);150(unshielded)