Model | SM 1223 DI 8×24 V DC DQ 8×RLY |
SM 1223 DI 16×24 V DC DQ 16×RLY |
SM 1223 DI 8×24 V DC DQ 8×24V DC |
Order number | UN 223-1PH32-0XB0 | UN 223-1PL32-0XB0 | UN 223-1BH32-0XB0 |
dimensionWxHxD(mm) | 45x100x75 | 70x100x75 | 45×100×75 |
weight | 230 g | 350g | 210g |
Power consumption | 5.5 W | 10 W | 2.5 W |
Current consumption (SM bus) | 145 mA | 180 mA | 145 mA |
Current consumption (24VDC) | Each point input used is 4mA 7mA per relay coil used |
Each point input used is 4mA 7mA per relay coil used |
150 mA |
UN 223-1PL32-0XB0
SM 1223 Digital input/output Module which is similar as Siemens S7-1200 PLC
1) SM 1223 Digital input/output 16DI 24V DC/ 16 Relay
2) Compatible with Siemens 6es7 223-1PL32-0XB0
3) Digital module;
4) Could connect with Siemens 1200 CPU and Modules;
5) 3-year warranty;
6) 2-3 working days after payment can ship;
7) Material: ABS, IC
Digital input
Enter points
8
16
8
Type
Sink/Source type (IEC Class 1 sink type)
Rated voltage
24V DC at 4 mA, nominal
Allowed continuous voltage
Max 30V DC
Surge voltage
35VDC, lasting 0.5s
Logic 1 signal (minimum)
2. 15V DC at 5mA
Logic 0 signal (maximum)
5 V DC at 1 mA
Isolation (field side and logic side)
707VDC (type test)
Isolation group
2
2
2
Filter time
0.2, 0.4, 0.8, 1.6, 3.2, 6.4 and 12.8ms (selectable, 4 in a group)
Number of inputs connected simultaneously
8
·8 (no adjacent points), at 60ºC (horizontal) or 50ºC (vertical)
·16, at 55ºC (horizontal) or 45ºC (vertical)
8
Cable length (meter)
500 (shielded); 300 (unshielded)
Digital output
Output points
8
16
8
Type
Relay, dry contact
Solid state -MOSFET (source type)
Voltage range
5-30VDC or 5-250VAC
20.4 -28.8V DC
Logic 1 signal at maximum current
–
Min20 V DC
Logic 0 signal with 10 KQ load
–
Max0.1V DC
Current (maximum)
2.0A
0.5 A
Lamp load
30 W DC/200 WAC
5 W
On-state contact resistance
0.2 Ω maximum for new equipment
Max0.6 Q
Leakage current per point
–
Max 10μA
Inrush current
7A with contacts closed
8A maximum duration 100 ms
Overload protection
None
Isolation (field side and logic side)
1500VAC (coil and contacts)
None (coil and logic side)
707V DC (type test)
Isolation group
2
4
1
Current at each common terminal
10 A
8A
4 A
Inductor clamping voltage
—
L+-48 V,1W loss
Switching delay
Maximum 10 ms
The longest time from disconnection to connection is 50μs
The longest time from connecting to disconnecting is 200μs
Mechanical life (no load)
10,000,000 open/close cycles
Contact life under rated load
100,000 open/close cycles
Behavior during RUN-STOP
Previous value or replacement value (default value is 0)
Number of outputs switched on simultaneously
8
·8 (no adjacent points), 60°C (horizontal) or 50°C (vertical)
·At 16,55ºC(horizontal) or 45ºC(vertical)
8